ABOUT FIRE ZONES
The Aegis 1000 system supports normally open (closed for alarm), two- -wire smoke detectors. Two wire smoke
detectors can only be connected to Zone 8. Four wire smoke detectors can be connected to any zone (1 8). An external 1000-
-of line resistor must be -wire or four
wire) or Gas zone, the Zone 8 Jumper (J9) must be
Smoke dete
End of line resistor: 1000 ohms. Maximum loop resistance end of line resistor is a 150 ohms. Use an End of
Line Resistor Assembly in UL Listed Installations.
3. Smoke detectors are reset when the security system is armed.
TWO WIRE SMOKE DETECTORS
Aegis 1000 supports two-
Use normally open (closed for alarm) two wire "SYSTEM" type smoke detectors (System Sensor 2100TS or equivalent),
- 14 VDC. A maximum of 10 2 wire smoke detectors can be connected.
2.
An external 1000 ohm end- -line resistor must be used.
4. Connect to the SWITCHED POWER OUTPUT as shown.
5. The Zone 8 Jumper (J9) must be in the SMK (smoke) position.
4. FIGURE 3 (TWO- for this configuration.
FOUR-
-wire smoke detectors connected to any zone -8).
1. Use normally open (closed for alarm) four-
rated 8 -
An End of Line Power Supervision Relay Module (System Sensor A77 716B or equivalent) is required for UL installations.
-ohm end of-
Power the smoke detector from SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
4. When connected to Zone 8, the Jumper (J9) must be in the SMK (smoke) position.
NOTE: nnected to Zone 8 are wired differently from those connected to Zones 1-
Refer to -WIRE FIRE ZONE CONNECTIONS)