Page 40
To change the alarm reset time, enter a new time between 1-30 minutes, then press the ' # ' key. The default setting is 4 minutes.
ARMING CONFIRMATION
The Arming Confirmation is a quick pulse (squawk) given by the exterior siren when the alarm system is armed into a security
mode and the EXIT DELAY is expired.
ARMING CONFIRMATION: 0
0=NO 1=YES ×
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key. The default setting is disabled.
FIRE ALARM VERIFICATION
This unit is equipped with a FIRE ALARM VERIFICATION feature. When a zone configured as a FIRE (Type 32) or a GAS
(Type 34) is activated, the system will cycle the SWITCH 12V Output off for 10 seconds. The SWITCH 12V Output will then be
restored, and 5 seconds later, the zones will be monitored again. If the zone is activated again within a 2-minute window, the fire
alarm will be activated. If not, no fire alarm will be indicated.
VERIFY FIRE ALARMS: 1
0=NO 1=YES ×
NOTE:
If VERIFY FIRE ALARMS is turned ON, any device (other than FIRE or GAS) connected to a SWITCH 12V Output (i.e.
Glassbreak Detectors), must be connected to a zone configured as a LATCHING ZONE TYPE.
This feature is designed to reduce false alarms and is turned ON by factory default. The following notice is required by UL:
WARNING
This unit includes an alarm verification feature that will result in a delay of the system fire alarm signal from the initiating
circuit. The total delay (Aegis 1000 controller plus detector delay) shall not exceed 60 seconds. No other initiating devices
shall be connected to these circuits unless approved by the local authority having jurisdiction.
Zone Control Detector Total Delay
Circuit Unit Delay Model/Delay
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
SUPERVISE BELL
This enables or disables supervision of the Bell Output, which monitors the wiring to bells and sirens. Factory default is disabled.
SUPERVISE BELL: 0
0=NO 1=YES ×
ENABLE EMERGENCY KEYS
This enables or disables the functionality of the emergency keys on the console keypad. Factory default is enabled.
ENABLE EMERG KEYS: 1
0=NO 1=YES ×